Method of
Communication is detected by checking the IPM module and the outdoor PCB
Malfunction
Detection
Malfunction ■
The outdoor PCB broken leads to communication fault
Decision
The IPM module broken leads to communication fault
Conditions
Supposed
The outdoor PCB is broken
Causes
The IPM module is broken
Communication wiring disconnected
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
NO
YES
NO
Are they good?
1) Pull out and reinsert the terminals.
2) Replace connected wire
1) Check whether Terminal CN14 and CN8 on the outdoor
mainboard CN10 and CN11 on IPM module
2) Check whether the connected wire between IPM and outdoor
YES
Replace the outdoor IPM module
with a new one.
Replace the outdoor mainboard with a new one
Electrify the machine again and turn it
on, Check whether the voltage between
1 and 2 of Terminal CN8 is about DC5V,
Check whether the voltage between2
and 3 of Terminal CN8 is about DC15V,
HSU-18,22HVA103/R2(DB) Service Diagnosis
80
Domestic Air Conditioner

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier HSU-22HVA103/R2(DB) and is the answer not in the manual?

Haier HSU-22HVA103/R2(DB) Specifications

General IconGeneral
BrandHaier
ModelHSU-22HVA103/R2(DB)
CategoryAir Conditioner
LanguageEnglish

Related product manuals