This product is responsible by special person, who will check the operation and record
every day (Record and check every 2-4h), the temperature in cabinet will rise in case of
machine fault or stop, if it can't be repaired in short time, please take out articles and move
to the places meeting storage temperature requirement, and avoid damage.
Before putting goods in this product for storage, confirm in advance that the temperature
for stored goods meets the temperature range of this product, for fear that the temperature
of this product can't reach the required temperature of stored goods and cause goods
damage, resulting in lose.
The actual display temperature has certain difference with setting temperature due to
refrigeration inertia (The lower the setting temperature of freezing chamber, the smaller the
temperature difference, and the greater the versa), this is normal.
Please unplug power plug when the refrigerator-freezer is not used for a long
time, and turn the batter switch to “O”, or it may cause electric shock, electric
leakage or fire due to aging power wire.
It is not allowed to put too many things one time, or it may cause compressor non-stop for
a long time, temperature falls slowly and will influence compressor life, goods should be
stored in batch, and temperature will fall ladderlike until the required temperature.
Don't damage refrigerating circuit.
use electrical appliance without the consent of the production in refrigerator-freezer.
Refrigerator-freezer has memory function for setting value, when it is power on after power failure,
refrigerator-freezer will continue running with the set parameters before last power failure.
Once the power of refrigerator-freezer is cut off, it needs to wait for 5min before
reconnection, or compressor or system may be damaged.
If refrigerator-freezer is not used for long time in area without monitoring, please
make sure children will not be close to the refrigerator-freezer, and the door
should not be closed fully.
Operation after Outage
10
Automatic recovery of alarm
This series of refrigerator has alarm automatic recovery function:
In case of alarm, press the buzzer cancel key on display board to stop buzzer alarm.
(Remote alarm will not stop)
If there is still alarm condition, buzzer alarm will automatically recover after stopping 30min.
Remote alarm terminal are loacted in top electric cabinet at the back of refrigerator-freezer.
Alarm signal output is carried out by these terminals with carrying capacity of DC 30V/2A.
Contact output:
In normal conditions, both ends of remote alarm terminals with connecting wire form open circuit.
In alarm conditons, both ends of remote alarm terminals with connecting wire form cloase circuit.
To use remote lalarm function, connect circuit as shown in the figure below.
Remote alarm terminal
Remote alarm function is limited to three alarm modes, i.e. high temperature
alarm, low temperature alarm and power failure alarm.
Blue wire connecting terminal
of remote alarm
Brown wire connecting terminal
of remote alarm
Alarm
DC power
supply
Connect to brown wire
connecting terminal of
remote alarm
Connect to blue wire
connecting terminal of
remote alarm