PU/PI and PS10 Instruction Manual
10
6 Technical data
0...50 Pa to 0...100 kPa or
±50 Pa to ±100 kPa
(others available upon request)
10 x the final value of the measurement range
(for measurement ranges 20 kPa)
2 x the final value of the measurement range
(for measurement ranges > 20 kPa)
time required for adjustment
approx. 20 ms (up to 5 s available upon request)
deviation from characteristic curve
0.5 % only for meas. ranges ≥250 Pa (optional)
0.2 % only for meas. ranges ≥250 Pa (optional)
2% for PS 10 model (others available upon request)
temperature-dependent drift in zero
point
0.04%/ K (in the +10°C...+50 °C range) for PU / PI model
0.1%/ K (in the +10°C...+50 °C range) for PS 10 model
temperature-dependent drift in
measurement range
0.04%/ K (in the +10°C...+50 °C range) for PU / PI model
0.1%/ K (in the +10°C...+50 °C range) for PS 10 model
approx. 2000 mm
3
(for measurement ranges 250 Pa)
approx. 9000 mm
3
(for measurement ranges 250 Pa)
air, all non-aggressive gases
EN 6100-6-3:2001 and EN 61000-6-2:2001; CSA
declaration of conformity available upon request