PU/PI and PS10 Instruction Manual
10
6 Technical data
Measurement data
measurement ranges
0...50 Pa to 0...100 kPa or
±50 Pa to ±100 kPa
(others available upon request)
overload capacity
10 x the final value of the measurement range
(for measurement ranges 20 kPa)
2 x the final value of the measurement range
(for measurement ranges > 20 kPa)
hysteresis
0.1 %
warm-up period
approx. 30 min.
time required for adjustment
approx. 20 ms (up to 5 s available upon request)
deviation from characteristic curve
(setting limiting value)
1 % for PU/PI model
0.5 % only for meas. ranges ≥250 Pa (optional)
0.2 % only for meas. ranges ≥250 Pa (optional)
2% for PS 10 model (others available upon request)
temperature-dependent drift in zero
point
0.04%/ K (in the +10°C...+50 °C range) for PU / PI model
0.1%/ K (in the +10°C...+50 °C range) for PS 10 model
temperature-dependent drift in
measurement range
0.04%/ K (in the +10°C...+50 °C range) for PU / PI model
0.1%/ K (in the +10°C...+50 °C range) for PS 10 model
dead volume
approx. 2000 mm
3
(for measurement ranges 250 Pa)
approx. 9000 mm
3
(for measurement ranges 250 Pa)
control volume
max. 200mm³
max. system pressure
100 kPa
Ambient conditions
medium
air, all non-aggressive gases
nominal temperature
+10° C to +50° C
operating temperature
0° C to +60° C
storage temperature
-10° C to +70° C
relative humidity
0…80 %
EMC standards
EN 6100-6-3:2001 and EN 61000-6-2:2001; CSA
conformity
declaration of conformity available upon request