EasyManua.ls Logo

Hansen APP08 User Manual

Hansen APP08
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Operator Installation
& Instruction Manual
AUTO-PURGER
®
PLUS, APP
Non-condensible Gas (Air) &
Water Purger for Ammonia
Bulletin APP-001b
APR 2007
Operator Installation & Instruction
Manual for Models APP08, APP16,
APP24 and APPC
AUTO-PURGER
®
PLUS, APP
SECTION 1 INTRODUCTION
The internal surface area and flooded evaporator efficiency
gives the AUTO-PURGER Plus two to three times the foul
gas condensing capacity of an Armstrong Purger and 10
times the capacity of purgers with small electric hermetic
compressors. In a system with normal noncondensible
loads, all models will handle a 750 ton (2600 kW) ammonia
plant at suction pressures below atmospheric pressure or
a 1500 ton (5300 kW) ammonia plant at positive suction
pressures. The amount of noncondensibles in the system
is based on many factors including age, maintenance
practices, and operating temperature.
The number of purgers required for a system depends on
the number of installed purge points. Twenty-four purge
points is the maximum practical number per purger. For
example, a system with 24 points set to purge for 10
minutes per point requires a 240 minute (4 hour) cycle.
Each purge point can be purged 6 times a day. This may, or
may not, be adequate. Therefore, a second purger should
be used and the purge points divided equally between
the two purgers.
The AUTO-PURGER Plus can operate over a wide range of
condensing pressures. This is important for refrigeration
systems that operate at low condensing pressures during
cold ambient conditions.
The AUTO-PURGER Plus is a totally automatic, electronically-
controlled refrigerant noncondensible gas (air) and
water purger for reducing the energy costs of operating
an ammonia refrigeration system. All models are pre-
assembled, pre-wired, insulated, and include an automatic
water bubbler, a relief valve, and an isolation service valve
package. Installation requires piping the foul gas line, low-
pressure pumped-liquid line, low-pressure liquid return
line, suction line, water bubbler fill and drain lines, relief
valve vent line, water purge line to a customer supplied
container, and power connection, and wiring the remote
purge point solenoid valves. Purge point solenoid valves
must be purchased separately and must be a minimum
of ½” (13 mm) port size.
In addition, a computerized model—APPC—is available
where a separate plant computer or programmable logic
controller (PLC) is used to independently operate the
various remote purge point solenoid valves.
Water contamination in an industrial ammonia refrigeration
system can lower system efficiency, and increase the
electrical costs required to run the system’s refrigeration
compressors. Ammonia refrigerant that is contaminated
with water requires a lower suction pressure to maintain
the same evaporator temperature than would pure
ammonia refrigerant. The requirement to maintain a
lower suction pressure than would be necessary if the
water contamination were removed is a waste of electrical
energy. For water removal, the AUTO-PURGER Plus has
the following capacities:
5% system water concentration – 3 gallons of water
removed per day
10% system water concentration – 5 gallons of water
removed per day
20% or more system water concentration – 7 gallons of
water removed per day.
Question and Answer IconNeed help?

Do you have a question about the Hansen APP08 and is the answer not in the manual?

Hansen APP08 Specifications

General IconGeneral
BrandHansen
ModelAPP08
CategoryAuto-Purgers
LanguageEnglish

Summary

SECTION 2 INSTALLATION

Mounting Instructions

Guidance for securely mounting the AUTO-PURGER Plus unit in the installation area.

Foul Gas Piping

Best practices for installing foul gas lines for optimal noncondensible gas removal.

Electrical Connections

Information on power supply requirements and electrical connection procedures.

SECTION 3 AUTO-PURGER PLUS OPERATION

Start-Up Procedure

Steps to follow for starting up the AUTO-PURGER Plus system.

SECTION 4 CONTROL CONSOLE OPERATION

Control Console Interface

Overview of the control console display, pushbuttons, and navigation.

SECTION 6 SERVICE, MAINTENANCE & PARTS

SECTION 7 TROUBLESHOOTING

Control Console Display 2222 (Foul Gas Pressure Loss)

Troubleshooting steps for loss of foul gas pressure indicated by display code 2222.

Control Console Display 3333 (Purger Too Warm)

Troubleshooting steps for the purger being too warm indicated by display code 3333.

Control Console Display 4444 (Purge Time Limit)

Troubleshooting steps for exceeding the 60-minute purge time limit (code 4444).

Control Console Display 7777 (Loss of Low-Pressure Pumped-Liquid)

Troubleshooting steps for insufficient liquid supply (code 7777).

Noncondensibles Not Being Released

Steps to diagnose why noncondensibles are not being released from the purger.

Ammonia Instead of Noncondensibles Released

Troubleshooting ammonia release instead of noncondensibles from the purger.

Ordering and Safety Information

Cautionary Notes

Important safety instructions and precautions for using the purger.

Related product manuals