SECTION 3 COMPONENT DESCRIPTIONS
AirPurgeLimit
PurgePointEnable
WaterCollecJon
DisplayUnits
MenuScreen1
Air Purge Limit – APPT can limit the amount on continuous
air purge time to 60 minutes during normal operation. If
there are large amounts of noncondensibles expected to
be present, for example during startup, this limit can be
disabled allowing the APPT to purge air continuously. To
change the selection, press /\ or \/ to enable or disable.
Purge Point Enable – APPT08 has purge points 01-08,
APPT16 has purge points 01-16, and APPT24 has purge
points 01-24. At system startup, when a purger is initially
installed in a system having fewer purge points than are
available on the APPT, the unused purge points must be
set to 0. To enable or skip a purge point simply touch
the purge point button on the screen and it will change
the selection.
Water Collection – This screen contains information
that can’t be changed. The counts indicate the time (in
seconds) the water concentration as measured by the
water concentration sensor (HPT717) exceeds the water
concentration set point. The concentration of water in the
purger evaporator must exceed 25% for 10 continuous
minutes AND have the low liquid level sensor reading wet
before the purger will enter Concentrating Water mode.
Drain Mode will always read 0 and can’t be changed.
Display Units – Changes the temperature and pressure
units for the display readout. To change the selection,
press /\ or \/ to switch the units.