1 2
Process-value (PV) display unit (Green)
Loop break alarm (LBA) action idicating lamp (Red)
Low alam (ALL) lamp (Red)
High alarm (ALH) lamp (Red)
Set-value increment Key
Set-value decrement Key
Mode (SET) Key
※DX9 basis
Setting digit shift Key
Set-value (SV) display unit (Red)
Auto-tuning (AT) lamp (Green)
Control output (OUT) lamp (Green)
※ 1 ALH and ALL are initialized if SL3 is changed.
※ 2 or ※ 3 is an option.
(The parameters are not shown if retransmission output is unavailable)
(The retransmission output option is not available for DX4, DX7.)
▒ Normal setting mode
※ Press the key continuously for 3 sec.
[ ] [ ] [ ] [ ]
Input type selection (Fixed)
SV display unit
PV display unit
(1) Press key and key simultaneously for 3 seconds to enter
the setting mode.
(2) Press key for 3 seconds to enter the PV / SV setting mode.
▒
Initial set mode
Process value
(PV) display unit
Name Description
High alarm (ALH) Displays high alarm set-value.
Low alarm(ALL) Displays low alarm set-value.
Proportional
band (P)
Set when proportional control is
performed. Control becomes ON/OFF
action with P set to “0” .
Anti-reset
windup (ARW)
Prevents overshoot and/or undershoot
caused by integral action effect. It operates
automatically (AUTO) if ARW is set to “0”.
Integral time
(I)
Eliminates offset occurring in proportional
control. Integral action is OFF with this
action set to “0”.
Derivative time
(D)
Prevents ripples by predicting output change
thereby improving control stability. Derivative
action is OFF with this action set to “0”.
Control loop
break alarm
(LBA)
Indicates control loop break alarm setting.
LBA is off if "0" is set.
Proportioning cycle
(C)
Displays control output cycle (sec.).
Hysteresis
(HYS)
Displays hysteresis of set-value for main
output. (ON/OFF control)
Full scale limit
This limits the maximum of retransmission
output.
Under scale
limit
This limits the minimum of retransmission
output.
Set data lock
(LOC)
Turns the set data lock ON/OFF
※3
※2
※1
※1
Set Description
0000 1 - 5 V d.c or 4 - 20
㎃
0001 K (CA)
0010 KPt100 Ω
0011 DIN Pt100 Ω
0100 R (PR)
0101 J (IC)
1111 0 - 10 V d.c
※1 : Set-value (SV) is a control target, It is settable within the input range.
▒
PV/SV display and SV setting modes
Process value
(PV) display unit
Set-value (SV)
display unit
Description
Process value
(PV)
Set-value (SV)
Displays process-value. Set-value
(SV) can be set ※1
Power supply voltage 100 – 240 V a.c (±10%), 50/60 Hz
Power consumption 4.5 W max
Input
Type Refer to input table
Sampling cycle
250 ms
Indication accuracy
± 0.5 % (refer to input type table)
Allowable voltage
20 Vd.c for 1 minute
Reference junction
compensation
accuracy
±3.5℃ (0 ~ 50℃)
Operation after input
break
Up Scale
Control
output
Relay
NO: 5 A 250 V a.c, 5A 30 V d.c (resistive load)
NC: 3 A 250 V a.c, 1A 30V d.c (resistive load)
Switching Life : 100 thousand times (without load)
Voltage output
ON voltage: 12 V d.c min
OFF voltage: 0.1 V d.c max
Load resistance 600Ω min
Current output
range: 3.2 ~ 20.8 mA
Accuracy: ± 0.2 mA
Load resistance 600Ω max
Retransmission output
range: 3.2 ~ 20.8 mA
Accuracy: ± 0.2 mA
Load resistance 600Ω max
Alarm output
5 A 250 V a.c, 5 A 30 V d.c (resistive load)
Switching Life: 100 thousand times (without load)
Control
method ON/OFF, PID control
Output operation
Reverse operation, Direct operation
Anti-reset
windup
Auto(A=0), 0.1 ~ 100%
Insulation resistance
20 MΩ min (primary terminal – secondary terminal)
Dielectric strength
2,300 V a.c, for 1 minute
(primary terminal – secondary terminal)
Operating
environment
Temper. & humidity
0 ~ 50℃, 35 ~ 85% R.H (with no condensation)
Environment Refer to safety information
Part name and functions
Specification
Operation
Caution
The value in the parameter SL1 (input selection) cannot be changed.
The SL1 is set according to the suffix code when ordering a product.