Harman PC45 - Venting Through Ceiling; Method #7 Installation

Harman PC45
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 pC 45 Corn/pellet Stove
3-90-02686R29_05/14
12"
min. above ground level
Minimum ue vent conguration
It is recommended that outside
air be installed with this venting
conguration.
Venting
Fig. 16
#7 Installing through the ceiling vent
Through the ceiling vent, follow PL vent manufacturers
recommendationswhenusingwallandceilingpassthrough.
PL vent manufacturer's
restop spacer and support
1" MIN.
No insulation or other
combustible materials
are allowed within 3"
of the PL vent pipe.
ashing
storm collar
1" MIN.
1" MIN.
12" MIN
1” MIN.
Fig. 15
12"
min. wall to outlet
36"
min. clearance to any
combustible material
Fig. 17
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST
VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
INSTALL VENT AT CLEARANCES SPECIFIED BY THE
MANUFACTURER
CAUTION
Keep combustible materials (such as grass, leaves, etc.) at
least 3 feet away from the ue outlet on the outside of the
building.
CAUTION
!
STOVE IS HOT WHILE IN OPERATION. KEEP
CHILDREN, CLOTHING, AND FURNITURE AWAY.
CONTACT MAY CAUSE SKIN BURNS.