11 pC 45 Corn/pellet Stove
3-90-02686R29_05/14
12"
min. above ground level
Minimum ue vent conguration
It is recommended that outside
air be installed with this venting
conguration.
Venting
Fig. 16
#7 Installing through the ceiling vent
Through the ceiling vent, follow PL vent manufacturers
recommendationswhenusingwallandceilingpassthrough.
PL vent manufacturer's
restop spacer and support
1" MIN.
No insulation or other
combustible materials
are allowed within 3"
of the PL vent pipe.
ashing
storm collar
1" MIN.
1" MIN.
12" MIN
1” MIN.
Fig. 15
12"
min. wall to outlet
36"
min. clearance to any
combustible material
Fig. 17
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST
VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
INSTALL VENT AT CLEARANCES SPECIFIED BY THE
MANUFACTURER
CAUTION
Keep combustible materials (such as grass, leaves, etc.) at
least 3 feet away from the ue outlet on the outside of the
building.
CAUTION
STOVE IS HOT WHILE IN OPERATION. KEEP
CHILDREN, CLOTHING, AND FURNITURE AWAY.
CONTACT MAY CAUSE SKIN BURNS.