9
XXV Pellet Stove
#1 Preferred method
This method provides excellent venting for nor-
mal operation and allows the stove to be installed
closest to the wall. Two inches from the wall is
safe; however, four inches allows better access to
remove the rear panel. The vertical portion of the
ventshouldbethreetovefeethigh.Thisvertical
section will help provide natural draft in the event of
a power failure. Note: Do not place joints within
wall pass-throughs.
Venting
Fig. 9
3 ft.
to combustibles
Fig. 10
12" min. wall to outlet
3 ft.
to combustibles
3 ft.
to combustibles
3 ft.
to combustibles
NOTICE
A chimney connector shall not pass through an attic or roof space, closet or similar
concealed space, or a oor, or ceiling.
Fig. 11
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be in-
stalled farther from the wall. The vertical portion of
theventshouldbethreetovefeethighandatleast
three inches from a combustible wall. This vertical
section will provide natural draft in the event of a
power failure.
If the stove is installed below grade be sure the
vent termination is at least 18" above grade. The
outlet must also be 1 foot from the house/building.
Note: Do not place joints within wall pass-
throughs.
CAUTION
Keep any materials that may be affected by the
elevated exhaust temperatures at least 3 feet
away from the ue termination.