34 Ceiling Cassette Air Conditioner
Troubleshooting Guide
When cooling does not operate
Trouble 3
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the
remote controller to at least 1°C(1.8ºF) below room temperature.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
Check the indoor temperature sensor is disconnected or not(About 10k / at
25°C(77°F)).
Check Relay(RY - COMP) for driving compressor.
When the power(About AC208V-230V) is applied to the connecting wire
terminal support transferred to compressor, PWB Ass'y is normal.
Check the circuit related to the relay.
Check point COMP ON COMP OFF
Below DC 1V
About DC12V
(app)
Between two pin of DC
part in relay for COMP