42 Ceiling Cassette Air Conditioner
Troubleshooting Guide
Troubleshooting CH24, CH25
24
25
Press S/W Open
Input voltage
Low / High press
S/W open.
Abnormal Input voltage
(140Vac , 300Vac .
Check the connection of CN_Press.
Check the components.
Check the power source.
Check the components.
Display
code
Title Cause of error Check point & Normal condition
Check Point
CH 24
1. Check the connection of CN_PRESS
2. Check the install condition for over load.
3. Check the SVC V/V open.
4. Check the leakage of refrigerant.
CH 25
1. Check the power source.
2. Check the components
(Trans1, B/Diode, Diode, Resistance)