for the technician
First firing, regulation and servicing instructions
Draining EURA boiler
To correctly drain both heating system and minitank in
the sanitary system, it is necessary to manually set three
way valve in middle position as described here below:
three way valve (item 3) must initially be in ‘sanitary’
mode (manual control spindle in position ‘S’). If it is
in position ‘R’, open a domestic hot water tap to move
it to ‘S’;
switch boiler off;
manually push spindle towards middle position,
where it can be blocked pushing towards inside
(position ‘C’).
Connect a rubber pipe to the draining tap [2] terminal;
put the other end of the pipe in a suitable drain or sink;
open draining tap anticlockwise;
when water pressure is COMPLETELY drained, you can
open radiators air vents, to allow air inlet and complete
plant draining;
when everything is over, close taps and air vents.