44
Installation EAGLE20/30
Release
06
04/2014
EMC and immunity
Note: You will find detailed information on the certificates and declarations applying to your device in a separate
overview.
See table 3 on page 18.
EMC interference
emission
Standard
applications
Navy applications Railway
applications
Substation
applications
Radiated emission
EN 55022 Class A — — Class A
GL Guidelines — EMC 1 — —
FCC 47 CFR Part 15 Class A — — Class A
EN 61000-6-4 Fulfilled — Fulfilled —
Conducted emission
EN 55022 AC and DC supply connections Class A — — Class A
GL Guidelines AC and DC supply connections — EMC 1 — —
FCC 47 CFR Part 15 AC and DC supply connections Class A — — Class A
EN 61000-6-4 AC and DC supply connections Fulfilled — Fulfilled —
EN 55022 Telecommunication connections Class A — — Class A
EN 61000-6-4 Telecommunication connections Fulfilled — Fulfilled —
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
Substation
applications
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge ± 4 kV ± 6 kV ± 6 kV ± 8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge ±8kV ±8kV ±8kV ±15kV
Electromagnetic field
EN 61000-4-3 80 MHz ... 3000 MHz 10 V/m 10 V/m — 10 V/m
EN 61000-4-3 80 MHz ... 2700 MHz — — 20 V/m —