19
10.1 Field Minimum Wire Sizes for Power Souce
Units Power supply
Power supply
wiring size
Communica
tion Cable
Size
Fan motor
Model Hz Volts
Voltage
range
MCA MOP kW FLA
AVS-07~09H3FSTD
60
208/
230V
Max.253V
Min.187V
0.70 15
Wiring size
and length
must
comply with
local codes.
AWG18*1
(0.82mm
2
)
0.03 0.37
AVS-12~14H3FSTD 0.72 0.03 0.37
AVS-18H3FSTD 0.97 0.06 0.52
AVS-22H3FSTD 1.02 0.06 0.52
AVS-24H3FSTD 1.07 0.06 0.52
NOTES:
MCA: Min. Circuit Amps (A) ; MOP: Max. Overcurrent Protective Device (A)
kW: Fan Motor Rated Output (kW) ; FLA: Full Load Amps (A)
(1) Use a shielded cable for the transmitting circuit and connect it to ground.
(2) Field wiring shall be in conformity to local laws and regulations, and all wiring operations must be performed by
qualified professionals.
(3) Once the power cord is damaged, the dealer or the professionals from designated maintenance department
must be contacted in a timely manner for repair and replacement.
15
15
15
15
Cut-Out
Cut-In
For Control Circuit
Fuse Capacity
Freeze Protection
Thermostat
A
3.15
0(32)
14(58)
Model
Indoor Unit
07~24
(°F)
(°F)