Figure 6 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Single-phase
1P32A-9C13-3C19CE.P)
Part
number Region Quantity
Power input
per PDU
Power
output per
PDU
Total rack
amperage
available
1P32A-9C1
3-3C19CE.P
APAC and
EMEA
6/rack
3/side
Single phase
230V max. 32A
(25.6A rated)
50Hz / 60Hz
Delta/wYe: N/A
IEC309 P + N +
E input power
plug
4.5 m (14.76
feet) cable
9 IEC C13 +
3 IEC C19
sockets
Max
allowable
current:
25.6A
5.9kVA
77A (17.6kVA)
APAC and EMEA single-phase PDU 1P32A-18C13-3C19CE.P
The following gure and table describe the specications of the PDU.
APAC and EMEA single-phase PDU 1P32A-18C13-3C19CE.P
Appendix E: Power distribution units for Hitachi Universal V2B Rack
Hitachi Virtual Storage Platform G350, G370 Hardware Reference Guide 120