● Table A: Optional Setting Items for Function Selection
No. Items Optional Function
Individual
Setting
Setting
Condition
Contents Setting
1 b1
Cancellation of Heating
Temperature Compensation
due to Uneven Heat Load
00
01
02
03
04
Standard (Set Temp. +4
o
C) (*1)
Removal (Set Temp.)
Set Temp. +2
o
C (*2)
Set Temp. +3
o
C
Set Temp. +1
o
C
2 b2
Circulator Function during
Heating Thermo-OFF
00
01
Not Available
Available
3 b3 Not Prepared
-
- Not Used (Use as 00 conditions)
4 b4 Change of Filter Cleaning Time
00
01
02
03
04
Standard (It depends on the model)
100 hrs
1,200 hrs
2,500 hrs
No Indication
5 b5 Fixing of Operation Mode
×
00
01
Standard
Fixed
6 b6 Fixing of Setting Temperature
×
00
01
Standard
Fixed
7 b7
Fixing of Operation as
Exclusive Cooling Unit
×
00
01
Standard
Fixed
8 b8 Automatic COOL/HEAT Operation
×
00
01
Not Available
Available
9 b9 Fixing of Fan Speed
×
00
01
Standard
Fixed
10 bA Not Prepared - - Not Used
11 bb
Cooling Temperature Compensation
due to Uneven Heat Load
00
01
02
Standard (No Compensation)
Set Temp. –1
o
C
Set Temp. –2
o
C
12 bC Not Prepared - - Not Used (Use as 00 conditions)
13 bd Not Prepared - - Not Used (Use as 00 conditions)
14 bE Not Prepared - - Not Used (Use as 00 conditions)
15 C1 Not Prepared - - Not Used (Use as 00 conditions)
16 C2 Not Prepared - - Not Used
17 C3 Not Prepared - - Not Used
18 C4 Not Prepared - - Not Used
19 C5
Hi Speed
(Except for Hi Speed during Heating
Thermo-OFF)
00
01
02
Standard
Hi Speed 1 (*3)
Hi Speed 2
20 C6
Hi Speed during Heating Thermo-
OFF
00
01
Not Available
Available
21 C7
Canceling of Enforced 3 Minutes
Minimum Operation Time of
Compressor
00
01
Standard
Cancelation
22 C8 Thermistor of Wired Controller
00
01
02
00
01
02
< If Wired Controller Thermistor is Selected ˃
Control by Indoor Suction Thermistor
Control by Thermistor of Wired Controller
Control by Average Value of Indoor Suction
Thermistor and Thermistor of Wired Controller
< If Remote Sensor is Selected ˃
Control by Average Value of Indoor Suction
Thermistor and Remote Sensor
Control by Remote Sensor
Same as "00"
23 C9 Not Prepared - - Not Used
24 CA Not Prepared - - Not Used
25 Cb Selection of Forced Stoppage Logic
00
01
Forced Stoppage Input: A Contact
Forced Stoppage Input: B Contact
26 CC Not Prepared - - Not Used (Use as 00 conditions)
27 Cd Not Prepared - - Not Used (Use as 00 conditions)
28 CE Not Prepared - - Not Used (Use as 00 conditions)