45
Ip (peak current cut)
LD301
Blinks 2
times
Blinks 3
times
Blinks 4
times
LD301
LD301
Self-diagnosis
Self-diagnosis lamp
and mode
Abnormal low speed
rotation
Switching incomplete
Fig. 4-5
Table 4-1
Fig. 4-4 Power module circuit (U
+
is OFF, V
is ON)
Since current flows at point B only when U
+
transistor and V
-
transistor are ON, the current waveform
at point B becomes intermittent waveform as shown in Fig. 4-3. Since current at point B is approximately
proportional to the input current of the air conditioner, input current is controlled by using DC current
(Id) detection resistor.
<Reference>
If power module is defected, self diagnosis lamps on the MAIN P.W.B. may indicate as shown below: