EasyManua.ls Logo

Hitachi RAK-35RPC - WEEKLY TIMER OPERATION

Hitachi RAK-35RPC
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CONTROL AND FUNCTION
2
2
9
9.2.
AUTO CHANGEOVER
COOLING/HEATING mode is decided by the room temperature.
A. COOLING/HEATING mode is decided during the
initial startup
of Automatic Operation
Initial startup of Automatic Operation means the
following either condition:
x Unit start up in Automatic Operation
x Automatic Operation mode is pressed while
the unit is running in manual mode
Startup room temperature COOL / HEAT
>= Remote controller
setting temperature
Unit runs in
COOLING mode
< Remote controller setting
temperature
Unit runs in
HEATING mode
B. COOLING/HEATING mode is decided i
in
intervals after the initial startup
of Automatic
Operation (also known as Auto Changeover
function)
Intervals Duration
1
s
t
10 minutesinterval
2
n
d
15 minutes interval
Subsequent interval Every 55 minutes
9.3.
SHIFT VALUE
1. Press and hold button and
(ON) button.
2. Press [RESET] button on the same time.
Release [RESET] button only, then
release and (ON) button
once Screen 1 appears.
Screen 1 Screen 2
3. Press the (MODE) button to display
fan mode (Screen 3).
Screen 3
4. Press and Screen 4 appear.
Screen 4
5. Select (FAN SPEED) button to choose
Heating Shift or Cooling Shift Mode (Screen 5).
By setting fan speed to HIGH or MED ,
it will go to Cooling Shift mode.
By setting fan speed to LOW or SILENT
, it will go to Heating Shift mode.
Screen 5
6. Press the Temperature button ( or ) to adjust the shift value.
Final preset
temperature
-3
o
C
+2
o
C
Heating
Cooling

Other manuals for Hitachi RAK-35RPC

Related product manuals