Hitachi RAS-18FH6 - CHECKING THE INDOOR UNIT ELECTRICAL PARTS; 4. Check the control P.W.B. (power circuit)

Hitachi RAS-18FH6
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74
1
2
2
1
4. Check the control P.W.B. (power circuit)
Is 35V or 20V being output
at pin 5 relative to 0V at
pin 3 of CN3?
Is 12V or 7V being output
at (+) relative to 0V at (-) of
C114?
Is ICP1 normal?
Normal if it is less than 1
.
Blown (open) if it is 1
or more.
Replace ICP1. Check if the air
deflector motor is shorted, and
IC111, Q111, C114, ZD121 are
defective.
If shorted / defective, ICP1 will be
open again.
Replace the terminal board.
Insert the connection cable
securely.
Replace IC121. Check if a short
occurs in the 5V line.
If the 5V line is shorted, ICP1 will
be open again.
Check to see if the connection cables are
disconnected or reversed.
If normal, check the outdoor unit P.W.B.
Has the terminal board
thermal fuse blown (open)?
Replace Q111 and IC111.
Is DC5V being generated?
Perform final operation check.
: When the unit is not in operation, the voltage across the 35V line may drop to 20V.
: When the unit is not in operation, the voltage across the 12 V line may drop to 7V.
Ye s
Ye s
(Normal)
Ye s
(Open)
Ye s
No
No
No
Ye s
No
No
RAS_AW_063-082e 11/17/06, 11:54 AM74