No. Setting item
7-segment display
Contents
SEG2 SEG1
17
Low noise setting (in the case of low
noise setting, the working range in
cooling/heating will be restricted)
db
00 Initial setting
01 Maximum fan rotation limit 20 steps
02 Maximum fan rotation limit 18 steps
03 Maximum fan rotation limit 16 steps
04 Frequency limit 1
05 Frequency limit 2
06 Frequency limit 3
07 operating sound value, catalogue value -2 dB (A)
08 operating sound value, catalogue value -5 dB (A)
09 operating sound value, catalogue value -8 dB (A)
18 Demand function setting dE
00 Without demand control
01 Demand control 40%
02 Demand control 60%
03 Demand control 70%
04 Demand control 80%
05 Demand control 100%
19 Wave function setting UE
00 Without wave function
01 Minimum limit 40%
02 Minimum limit 60%
03 Minimum limit 70%
04 Minimum limit 80%
20 Cold draft protection Fb
00 Initial setting
01
Outlet temperature 10 °C
02
Outlet temperature 12 °C
03
Outlet temperature 14 °C
21 Not prepared FT 00
22
Fan rotation adjustment (to prevent
humming noises in multiple
installation)
Fo
00 Initial setting
01 Change of fan rotation -15 rpm
02 Change of fan rotation -30 rpm
23 Not prepared LT 00
24 Not prepared F1 00
25 Not prepared F2 00
26 Not prepared F3 00
6.3.1 Indoor unit fan control during the Thermo-OFF in heating mode
1 Press
PSW3
and select the setting of the condition “1” of the indoor unit fan control during the Thermo-OFF in heating
mode “FA”.
2 When the fan speed is set lower for the Thermo-OFF in heating mode, there is a case in which the room temperature
is too high for the Thermo-OFF heating. In this case, it is recommended the indoor unit fan control during the Thermo-
OFF, and the detail of this function is shown below.
The indoor fan operates for 2 minutes and stops for 6 minutes repeatedly, when the activation conditions are met.