Abnormal transmission between outdoor units.
no. and alarm code are displayed on the outdoor unit's PCB1 display.
No
Yes
No
Yes
No
Yes
Is operating line between outdoor
unit A
and outdoor unit B connected
to H-LINK transmission terminal?
Is operating line between outdoor
unit A and outdoor unit C connected
to H-LINK transmission terminal?
Is operating line between outdoor
unit and outdoor unit connected
INCORRECTLY?
Correctly connect wiring between
outdoor unit and outdoor unit and
reset the power supply.
Abnormality of PCB1 in
outdoor unit A
Connect operating line between
outdoor unit A and outdoor unit B
to O.U.~O.U. transmission terminal.
Also, reset the power supply.
Connect operating line between
outdoor unit A and outdoor unit C
to O.U.~O.U. transmission terminal.
Also, reset the power supply.
(Sub): Secondary unit(s).
SMGB0065 rev. 1 - 12/2010