9.1. OUTDOOR UNITS INSTALLATION
CAUTION:
Transport the products as close to the installation location as
practical before unpacking.
Do not put any material on the products.
Apply four lifting wires on to the outdoor, when lifting it by crane
WARNING:
- Install the outdoor unit with sufcient clearance around it for
operation and maintenance as shown in the next gures.
Install the outdoor unit where good ventilation is available
- Do not install the outdoor unit where is a high level of oil mist,
salty air or sulphurous atmosphere.
- Install the outdoor unit as far as practical (being at least 3
meters) from electromagnetic wave radiator (such as medical
equipment).
- For cleaning, use noninammable and nontoxic cleaning liquid.
Use of inammable agent may cause explosion or re.
- Work with sufcient ventilation, for working in an enclosed space
may cause oxygen deciency. Toxic gas may be produced when
cleaning agent is heated to high temperature by, e.g., being
exposed to re.
- Cleaning liquid shall be collected after cleaning.
- Pay attention not to clamp cables when attaching the service
cover to avoid electric shock or re.
CAUTION:
Keep clearance between the units of more than 50mm, and
avoid obstacles that may hamper air intake, when installing more
than one units together.
Install the outdoor unit in the shade or not exposed to direct
sunshine or direct radiation from high temperature heat source.
Do not install the Outdoor Unit in a space where a seasonal wind
directly blows to the Outdoor fan.
Check to ensure that the foundation is at, level and sufciently
strong.
Install the unit in a restricted area not accessible by the general
public
Aluminum ns have very sharp edges. Pay attention to the ns to
avoid injury.
9. UNITS INSTALLATION