TC-12001
2-125
OUTDOOR UNIT
P5414950-rev.1
49
Do NOT operate the air conditioners to check
the electrical wiring, etc until the preparation of
the test run is completed.
(f) According to the label “Checking Method
by 7-Segment Display” attached to the rear
side of the service cover of the outdoor
unit, check the temperature, the pressure
DQGWKHRSHUDWLRQIUHTXHQF\RIVSHFL¿HG
portions, and check the connected indoor
unit numbers by 7-segment displays.
(g) 7R¿QLVKWKHWHVWUXQZDLWIRUKRXUVDV
default setting) or press “
“ (run / stop)
VZLWFKDJDLQ
O
)ODVKLQJWKHRSHUDWLRQODPSIRUVHFRQGV
21DQGVHFRQGV2))LVIRUDEQRUPDOLW\
RIWKHWUDQVPLWWLQJEHWZHHQWKHLQGRRUXQLW
DQGWKHUHPRWHFRQWUROVZLWFKORRVHQLQJ
or disconnecting connector, disconnecting
ZLUHVRULQFRUUHFWZLULQJHWF
O
Small sound may be heard from the
RXWGRRUXQLWDIWHUWXUQLQJ21WKHSRZHU
source because the electrical expansion
valve is activated to adjust the opening.
Therefore, there is no abnormality of the
unit.
O
Sound may be heard from the outdoor
unit for seconds after running or stopping
WKHFRPSUHVVRUVWDUWLQJRU¿QLVKLQJWKH
defrosting, etc. It generates because of
the pressure difference inside the piping
from the compressor. Therefore, there is
no abnormality of the unit.
(4) ,QWKHFDVHRIWKHWZLQWULSOHDQGTXDG
combination, check the air outlet temperature
of each indoor unit. If there is the large
GLIIHUHQWDLUÀRZWHPSHUDWXUHEHWZHHQHDFK
units (cooling: approx. more than 10deg,
KHDWLQJDSSUR[PRUHWKDQGHJLWPD\EH
WKHIDLOXUHRIWKHUHIULJHUDQWSLSLQJZRUN7KXV
recheck the refrigerant piping.