107
Ye s N o
No
Ye s
Ye s
Ye s
No
No
No
LD301 blinks 8 time.
Acceleration defect.
LD301 blinks 7 time.
Thermistor abnormal.
Is the power module normal?
Is the drive circuit normal?
Is the thermistor connector
disconnected?
The problem may be
forgetting
to connect after servicing
.
Is the continuity of thermistor normal?
Is the thermistor circuit normal?
Replace the power module.
Replace any defective parts.
Connect the thermistor.
Replace the thermistor.
Replace parts in the
thermistor circuit.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.