Installation and Maintenance
23
(1)
Prepare a polyvinyl chloride pipe with a 32mm outer diameter (3.0~6.5).
For Model1.5/2.0 : a300b500c50
For Model 3.0~6.5: a300b850c50,a+b+c1100
Prepare a polyvinyl chloride pipe with a 21mm inside diameter (1.5/2.0).
(2) Fasten the tubing to drain hose with the adhesive agent and factory-supplied clamp.The drain piping
must be performed with a down-slope pitch of 1/25 to 1/100.
* The total length of a+b+c :
* In case of lifting the drain pipe at outlet part, perform the drain piping work as shown in the
above figure.
(3) Insulate the drain pipe after connecting the drain hose.
Hose Band
(Accessory)
Hose Band
(Accessory)
Drain House
(Accessory)
Drain House
(Accessory)
1/25 to 1/100
Down-Slope
Vinyl Chloride
(Field Supplied)
Drain Pipe
Connection
850mm
Max.
Unit
Upward Slope
Rising part
Drain Pipe
Connection
1/25 to 1/100
Down-Slope
Common Drain Piping
This drain pipe shall be
separating from other pipes
Hose Band (Accessory)
Packing (5Tx270x270)
(Accessory)