26
Model
Capacity(HP)
Power
Supply
ELB
Power Source
Cable Size
Transmitting Cable
Size
Nominal
Current(A)
Nominal
Sensitive
Current (mA)
EN60335-1 EN60335-1
1.5
220-240V~, 50Hz
20 30
2
3×1.5mm
2
4×1.5mm
2.0
220-240V~, 50Hz
20 30
2
3×2.5mm
2
4×1.5mm
3.0
220-240V~, 50Hz
32 30
2
3×2.5mm
2
4×1.5mm
4.0
220-240V~, 50Hz
40 30
2
3×4.0mm
2
4×1.5mm
5.0/6.0/6.5
380-415V 3N~, 50Hz
32 30
2
5×2.5mm
2
4×1.5mm
Max. Running Current(A): REFER TO NAMEPLATE
Installation and MaintenanceInstallation and Maintenance
9. Electrical Installation
Use an ELB (Electric Leakage Breaker). If not used, it may cause an electric shock or a fire.
Do not operate the system until all the check points have been cleared.
(A) Check to ensure that the insulation resistance is more than 2MΩ, by measuring the
resistance between ground and the terminal of the electrical parts. If not, do not operate the
system until the electrical leakage is found and repaired.
(B) Check to ensure that the stop valves of the outdoor unit are fully opened and then start the
system.
NOTES:
1) Follow local codes and regulations when selecting field wires , and all the above are the minimum size.
2
) The wire sizes marked in the table are selected at the maximus current of the unit according to the
European Standard, EN60335-1. Use the wires which are not lighter than the ordinary polychloroprene
Place the round crimp-style terminals on the wires up to the
covered part and secure in place.
When connecting the terminal block using a single core
wire, be sure to perform curing.
3) When transmitting cable length is more than 15 meters, a larger wire size should be selected.
4) Use a shielded cable for the transmitting circuit and connect it to ground.
Flexible cord
sheathed flexible cord (code designation H07RN-F).
When connecting the terminal block using flexible cord, make sure to use the round crimp-style terminal
for connection to the power supply terminal block.
covered part
crimp-style terminal
Terminal
Single core wire
5)
In the case that power cables are connected in series, add each unit maximum current and select
wires below.
* In the case that current exceeds 63A, do not connect cables in series.
Current i(A)
2
Wire Size(mm)
i6
0.75
6i10 1
10i16 1.5
16i25 2.5
25i32 4
32i40 6
40i63
10
63i
*
Selection According to EN60335-1