Fault 
code 
Fault Description 
Possible Reason of Abnormality 
How to Deal With 
16  Low DC voltage 200V 
1.Voltage input too low ;
2.Driver board fault.
1.Check the power supply.
2.Change the driver board.
18 
Driver board read EE 
data error 
1.EEPROM has no data or data error;
2.EEPROM circuit fault.
1,Change EEPROM component;
2,Change the driver board. 
19 
PFC chip receive data 
fault 
Abnormal communication loop  Change the drive board. 
20 
PFC soft start 
abnormal 
Abnormal PFC drive loop  Change the drive board. 
21 
The compressor drive 
chip could not receive 
data from PFC chip. 
Communication loop fault.  Change the drive board.