Test in resistance.
TOOL: Multimeter.
Test the resistance of the winding.
The compressor is fault if the resistance of winding 0(short
circuit)oropen circuit
Familiar error:
1Compressor motor lock.
2Discharge pressure value approaches static pressure value .
3Compressor motor winding abnormality.
Notes
1Dont put a compressor on its side or turn over.
2) Please assembly the compressor in your air conditioner rapidly after removing the plugs. Don’t place
the comp. In air for along time.
3Avoiding compressor running in reverse caused by connecting electrical wire incorrectly.
4Warning! In case AC voltage is impressed to compressor, the compressor performance will below
because of its rotor magnetic force decreasing.
4. INDUCTANCE
Familiar error:
1Sound abnormality
2Insulation resistance disqualification.
5. STEP MOTOR
5
4
2
1
38