UNITS INSTALLATION
10.2. INSTALLATION SPACE
RAS-2~2.5 HVRN1
(mm)
a) In case of front side and either of the sides are open (single unit) b) In case that surrounding wall exist (single unit)
c) In case that upper side obstacles exist (single unit)
d) In case that upper side obstacles exist (serial units)
e) In case of front side and either of the sides are open (serial units)
f) In case that surrounding wall exist (serial units)
g) Horizontal (multiple units) h) Vertical (multiple units)
- Do not stack more than two units in height
- Close gap (*) to avoid recirculating discharge air flow
*
*
0 < L ≤ 1/2H → A ≥ 1000
1/2H < L ≤ H → A ≥ 350
0 < L ≤ 1/2H → A ≥ 600
1/2H < L ≤ H → A ≥ 1200
0 < L ≤ 1/2H → A ≥ 1000
1/2H < L ≤ H → A ≥ 350
0 < L ≤ 1/2H → A ≥ 200
1/2H < L ≤ H → A ≥ 350
0 < L ≤ 1/2H → A ≥ 600
1/2H < L ≤ H → A ≥ 1200
0 < L ≤ 1/2H → A ≥ 200
1/2H < L ≤ H → A ≥ 350