ELECTRICAL WIRING
25
13.3.2. WIRE SIZE
Recomended minimum sizes for field provided wires:
Power Source Cable Size Transmitting Cable Size
Model Power Source Max. Current
EN60 335-1
x
MLFC
y
EN60 335-1
x
MLFC
y
All Indoor Units
230V/1φ/50Hz
5 A 0.75 mm² 0.5 mm²
RAS-2HVRN1 16 A 1.5 mm² 0.75 mm²
RAS-2.5HVRN1
230V/1φ/50Hz
20 A 2.5 mm² 1.25 mm²
0.75 mm² 0.5 mm²
- The above wire sizes marked with x are selected
at the maximum current of the unit according to the
European Standard, EN60 335-1.
- The above wire sizes marked with y are selected at the
maximum current of the unit according to the wire, MLFC
(Flame Retardant Polyflex Wire) manufactured by
HITACHI Cable Ltd. Japan.
In case that the power cables are connected in series, add each unit maximum current and select according to the next table:
Selection according to
EN60 335-1
Selection according to MLFC (at
cable Temp. Of 60 ºC)
Current i (A) Wire Size (mm²) Current i (A) Wire Size (mm²)
I 6
0.75
I 15
0.5
6 < i 10
1
15 < i 18
0.75
10 < i 16
1.5
18 < i 24
1.25
16 < i 25
2.5
24 < i 34
2
25 < i 32
4
34 < i 47
3.5
32 < i 40
6
47 < i 62
5.5
40 < i 63
10
62 < i 78
8
63 < i
z
78 < i 112
14
112 < i 147
22
z In case that current exceeds 63 A do not connect cables in series
NOTE:
- Follow local codes and regulations when selecting field wires, Circuit breakers and Earth Leakage breakers
- Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord (code designation
H05RN-F)
Select the main switches in according to the next table:
Model Power Source
Max.
Current
CB
ELB
(no. poles/A/Ma)
All Indoor Units
230V/1φ/50Hz
5 A 6 A
RAS-2HVRN1 16 A 16 A
RAS-2.5HVRN1
230V/1φ/50Hz
20 A 20 A
2/20/30
ELB: Earth switch; CB: Switch.