•  Example of Wiring Connection (Twin, Triple and Quad Combinations for Simultaneous Operation)
Control cable
Shielded twist pair cable 0.75 mm
2
 
This cable does not need any polarity. 
Do not apply an excessively high voltage to 
this cable. (Rated voltage: 5V) 
Connect to both ends of shield tube to earth.
Remote control switch 
(Option)
Outdoor unit
Indoor unit number 1
Main 
switch
Power source cable
Pay attention to the 
phase of power source 
when wiring.
Indoor unit number 4
Indoor unit number 3
Indoor unit number 2
Main switch
Pull box
Remote control switch cable (Field supplied)
2 core twist pair cable 0.75 mm
2
. This cable 
does not need any polarity. Do not apply an 
excessively high voltage to this cable.  
(Rated voltage: 5V) 
Connect to both ends of shield tube to earth.
The details of wire, ELB, CB and 
main switch for outdoor unit shall be 
referred to Installation and Operation 
Manual of connected outdoor unit.
Pull box Pull box
Earth 
wiring
•  Example of Wiring Connection (Twin, Triple and Quad Combinations for Individual Operation)
Remote control 
switch (Option)
Outdoor unit Indoor unit number 1Main 
switch
Power source cable
Pay attention to the 
phase of power source 
when wiring.
Indoor unit number 4
Indoor unit number 3
Indoor unit number 2
Main switch
Pull box
Remote control switch cable 
(Field supplied)
2 core twist pair cable 0.75 mm
2
 
This cable does not need any polarity. 
Do not apply an excessively high voltage to this 
cable. (Rated voltage: 5V) 
Connect to both ends of shield tube to earth.
The details of wire, ELB, CB 
and main switch for outdoor unit 
shall be referred to Installation 
and Operation Manual of 
connected outdoor unit.
Pull box
Pull box
Remote control 
switch (Option)
Remote control 
switch (Option)
Control cable
Shielded twist pair cable 0.75 mm
2
 
This cable does not need any polarity. 
Do not apply an excessively high voltage 
to this cable. (Rated voltage: 5V) 
Connect to both ends of shield tube to 
earth.
Remote control 
switch (Option)
Earth 
wiring
Model ELB Main switch CB (Fuse) Wiring size (mm
2
)
Combination
(n/A/mA)
Rated 
current (A)
Rated 
current (A)
Power 
source cable
Transition wiring between OU and IU
Earth 
wiring 
*7
Remote 
control 
switch  cable  
*8
Power supply
Control circuit *5
*1 *2 *2 *3 *6 < 20m *4
Single type
2/40/30 5 5
0.75
1.0 0.75
0.75
0.75
Twin, Triple, Quad 1.0 1.0
ELB: Earth Leakage Breaker; CB: Circuit Breaker; IU: Indoor unit; OU: Outdoor unit
? NOTE
For the total wiring length more than 20m, refer to Installation and Operation Manual of the outdoor unit.
ELECTRICAL WIRING