10  Servicing
340
SMGB0077 rev.0 - 01/2013
10.4.10  Removal of the electronic expansion valve coil
Secure  the  body  of  the  valve  using  an  appropriate  wrench  and 
loosen the nut with another wrench, turning it anti-clockwise.
N O T E
Do  not hold  onto  the  motor  when  loosening  the  nut  with a 
wrench.  The  base  of  the  transmission  part  could  become 
loose and break.
 
Remove the optional air panel in line with the instructions given in 
chapter Removal of the optional air panel.
 
Remove the fan duct and the fan as indicated in chapter Removal of the fan duct and the fan.
Remove the drain pan as indicated in chapter Removal of the drain pan.
Loosen the nut several turns to release the transmission part from the bolt.
Prepare the  new  transmission  part  (spare part)  with  the position  of  the transmission  wheel  (transmission bolt)  already 
adjusted.
N O T E
•  Pay  attention  to  removal  while  replacing  and  prevent  dust  and  foreign  particles,  etc.  from  entering  it  (the 
exposed part during removal is the mechanical part of the valve).
•  Do not damage the valve joint with tools.
 
Fit the transmission part to the body of the valve, hold onto both and make sure their axes coincide before tting the nut 
to the valve body bolt.
Tighten the nut by hand and apply the torque value: 12 Nm - 15 Nm.
N O T E
•  Do not apply signicant force to the motor, such as
rotational  torque  or  bending  load,  while  holding  it  with 
your hand and tightening the nut.
•  Thedirectionoftheeccentricpartofthemotoristtedin
the same way as the expansion valve. Although the motor 
is facing away from the piping  connections on  the valve 
body, modication of this direction does not affect the
valve open/close function.  Therefore,  it is not necessary 
to adjust the direction of the motor if the motor position 
moves  in  the  direction  of  rotation  after  replacement,  as 
showninthegure.
•  However, check that the motor direction for the electronic 
expansion valve  coil does not touch  another pipe or  the 
side plate of the electrical box.
 
Once  replaced,  t the  electronic  expansion  valve in  the  reverse 
manner as indicated for the removal process.
Position the butyl sheet, attaching it correctly to the valve.
 
N O T E