39
INSTALLATION AND OPERATION MANUAL
ENGLISH
15.2. TEST RUN FROM OUTDOOR UNIT SIDE
The procedure of test run from outdoor unit side is indicated below. 
Setting of this DIP switch is available with the power source ON.
 WARNING:
 − Do not touch any other electrical parts when operating 
switches on the PCB.
 − Do not attach or detach service cover when the power 
source for the outdoor unit is ON and the outdoor unit 
is operated.
 − Turn all DIP switches of DSW1 OFF when the test run 
operation is completed.
Setting of Dip Switch (Before Shipment)
DSW1
Switch for setting of Serivice Operation and Function
1.  Test Run
2.  COOL/HEAT
  Setting (ON: Heat Operation)
3.  OFF (Fixed)
4.  Manual Compressor OFF
Operation Dip Switch Setting Operation Remarks
Test Run
  Setting of Operation Mode:
  Cooling: Set DSW1-2 OFF.
  Heating: Set DSW1-2 ON.
Starting Test Run:
  Set DSW1-1 ON and the operation 
is started after a few ~20 seconds.
  When heating operation, leave 
DSW1-2 at ON
     ↓
  The indoor unit automatically start 
to operate when the test run of the 
outdoor unit is set.
  The ON/OFF operation can be 
performed from the remote control 
switch or DSW1-1 of the outdoor 
unit.
  Continuous operation during 2 
hours is performed without Thermo-
OFF.
 NOTE:
TEST RUN operation time can 
be increased depressing the time 
switch in the Remote Control.
  Take care that the indoor units start 
operation in accord with the test run 
operation of the outdoor unit.
  The test run is started from the outdoor 
unit and stopped from the remote control 
switch, the test run function of the remote 
control switch is cancelled. However, the 
test run function of the outdoor unit is not 
cancelled
  In case that the plural indoor units are 
connected with one remote control 
switch, all the units start test run 
operation at the same time, therefore, 
turn the power source OFF for the indoor 
units not to operate test run. In this case, 
the “TEST RUN” indication of the remote 
control switch may icker, and this is not 
abnormal.
  The setting of DSW1 is not required 
for the test run from the remote control 
switch.
Manual OFF of 
Compressor
  Setting:
Compressor Manual OFF:
  Set DSW1-4 ON.
  Compressor ON:
  Set DSW1-4 OFF. 
  When DSW1-4 is ON during 
compressor operation, the 
compressor stops to operate 
immediately and the indoor unit is 
under the condition of Thermo-OFF.
  When DSW1-4 is OFF, the 
compressor starts to operate after 
the cancellation of 3-minutes guard.
  Do not repeat compressor ON/OFF 
frequently.
Manual 
Defrost
  Manual Defrost Operation Starts
  Press PSW1 for more than 3 
seconds during heating operation, 
the defrost operation is started 
after 2 minutes.This function is not 
available within 5 minutes after 
starting heating operation
  Manual Defrost Operation Finishes
  Defrost operation is automatically 
ended and the heating operation is 
started.
Defrost operation is available 
regardless of frosting condition and 
total time of heating operation.
Defrost operation in not performed 
when the temperature of outdoor 
heat exchanger is higher than 
10°C, high pressure is higher than 
3.3 MPa (33kgf/cm
2
G) or Thermo-
OFF.
  Do not repeat defrost operation 
frequently.
PMML0197_r0_04-10.indb   39 08/07/2010   9:21:00