! CAUTION
•  Wrap the  accessory packing around  the wires, and plug the  wiring 
connection hole with the seal material to protect the product from any 
condensate water or insects.
•  Tightly secure the wires with the cord clamp inside the indoor unit.
•  Lead  the  wires  through  the  knockout  hole  in  the  side  cover  when 
using conduit.
•  Secure the cable of the remote control switch using the cord clamp 
inside the electrical box.
? NOTE
The procedure of the wiring work shall  be  performed  according  to  this 
manual and Installation and Operation Manual of the outdoor unit.
15.1 GENERAL CHECK
1  Make sure that the eld-selected electrical components (main 
power switches, circuit breakers, wires, conduit connectors 
and wire terminals) have been properly selected according to 
the electrical data given in “Technical Catalog”. Make sure that 
the components comply with National Electrical Code (NEC).
2  Use the shielded twist pair cable for the control cable between 
the outdoor unit and the indoor unit, the control cable between 
indoor units and the remote control switch cable.
3  Check to ensure that the power supply voltage is within 
±10% of the rated voltage.
4  Check the capacity of the electrical wires. If the power 
source capacity is too low, the system cannot be started due 
to the voltage drop.
5  Check to ensure that the earth wire is connected.
15.2 ELECTRICAL WIRING CAPACITY
15.2.1   Field minimum wire sizes for power source
•  Do not operate the system until all the check points have 
been cleared.
a.  Check to ensure that the electrical resistance is more 
than 1 megohm, by measuring the resistance between 
ground and the terminal of the electrical parts. If not, 
do not operate the system until the electrical leakage is 
found and repaired. Check to ensure that the stop valves 
of the outdoor unit are fully opened, and then start the 
system.
b.  Check to ensure that the switch on the main power 
source has been ON for more than 12 hours, to warm the 
compressor oil by the crankcase heater.
•  Do not touch any of the parts by hand at the discharge gas 
side, since the compressor chamber and the pipes at the 
discharge side are heated higher than 90ºC.
Model
Power 
source
Maximum 
current - 
operation 
(A)
Power 
source 
cable size
Transmitting 
cable size
EN 60335-
1 *1
EN 60335-
1 *1
RPC-1.5FSR
1~ 230V 
50Hz
0.7
0.75 mm
2
0.75 mm
2
RPC-2.0FSR 0.7
RPC-2.5FSR 0.9
RPC-3.0FSR 0.9
RPC-4.0FSR 2.4
RPC-5.0FSR 2.4
RPC-6.0FSR 2.4
? NOTE
•  Follow local codes and regulations when selecting eld wires.
•  The wire sizes marked with *1 in the above table are selected at the 
maximum  current  of  the  unit  according  to  the  European  Standard, 
EN 60335-1. Use  the  wires  which  are not lighter than  the  ordinary 
tough rubber sheathed exible cord (code designation 60245 IEC 57) 
or ordinary polychloroprene sheathed exible cord (code designation 
60245 IEC 57).
•  Use  a  shielded  cable  for  the  transmitting  circuit  and  connect  it  to 
ground.
•  In the case that power cables are connected in series, add each unit 
maximum current and select wires below.
Selection according to EN 60335-1
Current i (A) Wire size (mm
2
)
i < 6 0.75
6 < i < 10 1
10 < i < 16 1.5
16 < i < 25 2.5
25 < i < 32 4
32 < i < 40 6
40 < i < 63 10
63 < i
In the case that current exceeds 
63 A, do not connect cables in 
series.
ELECTRICAL WIRING
PMML0551 rev.4 - 07/2023 - A10762310A
23
EN