30
INSTALLATION AND OPERATION MANUAL
11.5. CAUTION OF THE PRESSURE BY CHECK 
JOINT
When the pressure is measured, use the check joint of gas stop valve (A), 
and use the check joint of liquid piping (B) in the gure below.
At that time, connect the pressure gauge according to the following 
table because of high pressure side and low pressure side changes by 
operation mode.
Cooling 
Operation
Heating 
Operation
Check Joint for Gas Stop Valve “A” Low Pressure High Pressure
Check Joint for Piping “B” High Pressure Low Pressure
Check Joint for Liquid Stop Valve “C”
Exclussive for Vacuum Pump 
and Refrigerant Charge
 NOTE:
Be careful that refrigerant and oil do not splash to the electrical parts 
at removing the charge hoses.
RAS-5H(V)RNM1E
RAS-3HVRNME
The below gures show 
examples of 3 and 5 HP
11.6.  REFRIGERANT CHARGING QUANTITY
Outdoor Units has been charged with refrigerant for ℓ(m) of actual piping 
length. An additional refrigerant charged is required in systems with actual 
piping length longer than ℓ(m).
1. Determine an additional refrigerant quantity according to the following 
procedure, and charge it into the system.
2. Record the additional refrigerant quantity to facilitate service activities 
thereafter.
 CAUTION:
When charging refrigerant accurately measure refrigerant to be 
charged.
Overcharging or undercharging of refrigerant can cause 
compressor trouble
In case of actual piping length less than 5 m, consult your 
distributor.
  Outdoor unit Factory Refrigerant charge (Wo Kg) is the next:
O/U MODEL Wo (Kg)
Chargeless 
Length ℓ(m)
Additional Charge 
Factor (P)
RAS-3HVRNME 2.4 30 0.04
RAS-4H(V)RNM1E 3.9 30 0.06
RAS-5H(V)RNM1E 3.8 30 0.06
RAS-6H(V)RNM1E 3.8 30 0.06
RAS-4HVRNS1E 2.8 20 0.04
RAS-5HVRNS1E 2.9 30 0.06
RAS-6HVRNS1E 2.9 30 0.06
a) Refrigerant shall be added if L is longer than the chargeles length 
shown in the table above. 
Calculate the additional amount as follows:
L= A+B+C= 30+8+8= 46
RCI-2.0FSN2E
RCI-2.0FSN2E
RAS-4HVRNM1E
 - Chargeless Length ℓ: for 4HVRNM1E is 30 m according to the 
table before.
 - Additional Correction Value P: for 4HVRNM1E, “0.06” according to 
the table above.
 - Additional Charge amount W will be:
W= (L-ℓ) x P = (46-30) x 0.06 = 0.96 (kg)
b) Charge the amount W calculated by a)
c) Setting of Pipe Length DSW. 
DSW2 setting will be required only when the refrigerant pipe length 
is shorter than 5 m or longer than 30 m. Pipe length setting shall be 
performed as shown below.
(The  side in the table below shows the DSW location)
DSW2 on Outdoor PCB1
Factory setting Factory setting Factory setting
Pipe Length 5 m or 
shorter
Pipe Length 30 m or 
longer
11.7. PUMP DOWN REFRIGERANT
When the refrigerant should be collected into the outdoor unit due to 
indoor/outdoor unit relocation, collect the refrigerant as follows:
1. Attach the manifold gauge to the gas stop valve and the liquid stop 
valve
2. Turn ON the power source
3. Set the DSW1-1 pin of the outdoor unit PCB at the “ON” side 
for cooling operation. Close the liquid stop valve and collect the 
refrigerant.
4. When the pressure at lower pressure side (gas stop valve) indicates 
-0.01 MPa (-100 mmHg), perform the following procedures 
immediately.
 − Close the gas stop valve.
 − Set the DSW1-1 pin at the “OFF” side (To stop the unit operation).
5. Turn OFF the power source.
 CAUTION:
Measure the low pressure by the pressure gauge and keep it not to 
decrease than -0.01 MPa. If the pressure is lower than -0.01 MPa, 
the compressor may be faulty.
PMML0197_r0_04-10.indb   30 08/07/2010   9:20:49