Hitachi RPI-0.8FSN4E - SETTING OF THE DSW SWITCHES ON PCB1

Hitachi RPI-0.8FSN4E
756 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A
Main outdoor unit
A1
Secondary outdoor unit
B
Operation wiring (shielded twisted pair cable or shielded pair
cable) 5 V DC non-polar H-LINK (eld-supplied)
C
Distribution box (eld-supplied)
D
Indoor units
E
Remote control wire (shielded twisted pair cable or shielded pair
cable) (eld-supplied)
F
Fuse or CB(eld-supplied)
G
Remote control
H
Indoor unit system number 0
I
Indoor unit system nubmer 1
J
Transmission wire between A and A1
K
CH unit
CB
Circuit breaker (eld-supplied)
ELB
Earth Leakage Breaker (eld-supplied)
Connection diagram: heat pump system
A1
B
TB1
3N
400V/50Hz
1N
220-240V/50Hz
230V/50Hz
3N
400V/50Hz
TB1TB2
L1 L2 L3 N1234
TB2
1234
TB1
L1 L2 L3 N
12AB
TB2
12AB
TB2
TB1
L1 L2 NL1L2N
ELB
ELB
ELB
CC
D
D
EE
F
F
F
G G
HI
CB
CB
CB
ELB
ELB
ELB
J
Location of the DSW switches on PCB1.
SEG2
DSW6
DSW5
PSW3
SEG1
DSW4
DSW3DSW2
PSW2
PSW1
DSW7
DSW10
PSW4
PSW5
DSW1
RSW1
< PCB1 >
CAUTION
Before changing the settings of the DIP switches, the voltage
supply should be disconnected. Otherwise, the new settings will
not be valid.
NOTE
Only the DIP DSW1, DSW2 and DSW4 switches can be set
while the voltage supply is connected.
The symbol “■” indicates the position of the DIP switches. The
gures show the position of the DIP switch once the position
setting has been completed.
With the DSW4 switch, the unit starts or stops after
10 to 20 sec. of the switch being enabled.
Record the number of the outdoor unit to tell it apart from oth-
ers during service and maintenance operations in this area:
PSW1
PSW2
PSW3PSW5
PSW4
PSW buttons on PCB1
PSW1: accept.
PSW2, 3, 4 and 5: for checking.
DSW1, RSW1: refrigerant cycle number setting
Setting required
Setting before RSW1 supply: 0
Setting before DSW1 supply: 0 (digit of tens)
Set each main outdoor unit number on each
refrigerant cycle (Subs-units setting are not
required)
Outdoor and indoor units belonging to the
same refrigerant cycle: setting the same
cycle number in the outdoor and indoor units
(indoor units: DSW5 and RSW2)
10.5 SETTING OF THE DSW SWITCHES ON PCB1
64
PMML0294A rev.2 - 07/2014
Electrical wiring