•  or heat pump systems (2 pipes)
Model RAS-50FSXN1E RAS-52FSXN1E RAS-54FSXN1E
Combination unit
Outdoor unit A RAS-14FSXN1E RAS-14FSXN1E RAS-16FSXN1E
Outdoor unit B RAS-14FSXN1E RAS-14FSXN1E RAS-14FSXN1E
Outdoor unit C RAS-12FSXN1E RAS-12FSXN1E RAS-12FSXN1E
Outdoor unit D RAS-10FSXN1E RAS-12FSXN1E RAS-12FSXN1E
Piping connection kit MC-40AN1
Piping size  
(Ø mm)
a
High/Low pressure gas 38.1 (38.1-41.3) 38.1 (38.1-41.3) 38.1 (38.1-41.3)
Liquid 19.05 (19.05-22.2) 19.05 (19.05-22.2) 19.05 (19.05-22.2)
b
High/Low pressure gas 31.75 (31.75-34.9) 31.75 (31.75-34.9) 31.75 (31.75-34.9)
Liquid 19.05 (19.05-22.2) 19.05 (19.05-22.2) 19.05 (19.05-22.2)
c
High/Low pressure gas 25.4 (25.4-28.58) 25.4 (25.4-28.58) 28.58 (28.58-31.75)
Liquid 12.7 (12.7-15.88) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
d
High/Low pressure gas 25.4 (25.4-28.58) 25.4 (25.4-28.58) 25.4 (25.4-28.58)
Liquid 12.7 (12.7-15.88) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
e
High/Low pressure gas 25.4 (25.4-28.58) 25.4 (25.4-28.58) 25.4 (25.4-28.58)
Liquid 12.7 (12.7-15.88) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
f
High/Low pressure gas 22.2 (22.2-25.4) 25.4 (25.4-28.58) 25.4 (25.4-28.58)
Liquid 9.52 (9.52-12.7) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
•  For heat recovery systems (3 pipes)
Model RAS-50FSXN1E RAS-52FSXN1E RAS-54FSXN1E
Unit A RAS-14FSXN1E RAS-14FSXN1E RAS-16FSXN1E
Unit B RAS-14FSXN1E RAS-14FSXN1E RAS-14FSXN1E
Unit C RAS-12FSXN1E RAS-12FSXN1E RAS-12FSXN1E
Unit D RAS-10FSXN1E RAS-12FSXN1E RAS-12FSXN1E
Connection kit MC-40XN1
Piping sizes  
(Ø mm)
a
Gas (low pressure) 38.1 (38.1-41.3) 38.1 (38.1-41.3) 38.1 (38.1-41.3)
Gas (high/low pressure) 31.75 (31.75-34.9) 31.75 (31.75-34.9) 31.75 (31.75-34.9)
Liquid 19.05 (19.05-22.2) 19.05 (19.05-22.2) 19.05 (19.05-22.2)
b
Gas (low pressure) 31.75 (31.75-34.9) 31.75 (31.75-34.9) 31.75 (31.75-34.9)
Gas (high/low pressure) 28.58 (28.58-31.75) 28.58 (28.58-31.75) 28.58 (28.58-31.75)
Liquid 19.05 (19.05-22.2) 19.05 (19.05-22.2) 19.05 (19.05-22.2)
c
Gas (low pressure) 25.4 (25.4-28.58) 25.4 (25.4-28.58) 28.58 (28.58-31.75)
Gas (high/low pressure) 22.2 (22.2-25.4) 22.2 (22.2-25.4) 22.2 (22.2-25.4)
Liquid 12.7 (12.7-15.88) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
d
Gas (low pressure) 25.4 (25.4-28.58) 25.4 (25.4-28.58) 25.4 (25.4-28.58)
Gas (high/low pressure) 22.2 (22.2-25.4) 22.2 (22.2-25.4) 22.2 (22.2-25.4)
Liquid 12.7 (12.7-15.88) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
e
Gas (low pressure) 25.4 (25.4-28.58) 25.4 (25.4-28.58) 25.4 (25.4-28.58)
Gas (high/low pressure) 22.2 (22.2-25.4) 22.2 (22.2-25.4) 22.2 (22.2-25.4)
Liquid 12.7 (12.7-15.88) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
f
Gas (low pressure) 22.2 (22.2-25.4) 25.4 (25.4-28.58) 25.4 (25.4-28.58)
Gas (high/low pressure) 19.05 (19.05-22.2) 22.2 (22.2-25.4) 22.2 (22.2-25.4)
Liquid 9.52 (9.52 - 12.7) 12.7 (12.7-15.88) 12.7 (12.7-15.88)
Perform the installation of the outdoor unit and piping connection according to the gure. Refer to the table for the outdoor unit model, 
the piping connection kit model and the piping diameter.
If the main refrigerant pipe specied in the table is not available at the installation location, select the size given in brackets. In this 
case, prepare a suitable reducer.
39
PMML0294A rev.2 - 07/2014
Piping work and refrigerant charge
PMML0294A_rev.2_02-2014.indb   39 14/07/2014   12:28:25