10.3 COMMON WIRING
! CAUTION
Alltheeldwiringandelectricalcomponentsmustcomplywithlocalcodesandregulations.
10.3.1  Electrical wiring between indoor unit and outdoor unit
 Connect the electrical wires between the indoor unit and the 
outdoor unit, as shown below.
 Open a hole near the connection hole of power source 
wiring when multiple outdoor units are connected from one 
power source line.
 The recommended breaker sizes are detailed in the Wire 
size section.
 
rubber bushes with adhesive on the panel.
Power source from the outdoor unit to the indoor unit (example) Independent power source of outdoor unit and indoor unit (example)
3
3
3
L1   L2   L3    NL1   L2   L3    N
L1   L2   L3    N
Nº 0 System 
Outdoor unit
Nº 0 System 
Outdoor unit
Operating Line 
(Shielded Pair Cable)
DC5V (Non-Pole Transmission,
 
H-LINK System)
Remote Control Switch 
(Twisted Shielded Pair Cable)
Operating Line 
(Twisted Shielded 
Pair Cable)
DC5V (Non-Pole 
Transmission, H-LINK 
System)
Indoor Unit Indoor Unit
Terminal board
Circuit Breaker
Earth leakage Breaker
Field Wiring
Field supplied
Optional Accessory
Remote Control Switch 
(Twisted Shielded Pair Cable)
Indoor Unit
Indoor Unit
10.3.2  Wire size
 
Connection wiring
Model Power supply
Power 
source 
cable size
Transmitting 
cable size
EN60335-1 EN60335-1
All Indoor Units  
(except 8, 10, 16 and 
20HP)
1~ 230V 50Hz 
or 
1~ 220-
240V 50Hz 
(depending on 
the model)
0.75 mm²
0.75 mm²
 1~ 230V 50Hz 6.0 mm
2
 3N~ 400V 50Hz 4.0 mm
2
? NOTE
• Followlocalcodesandregulationswhenselectingeldwires,Circuit
breakersandEarthLeakagebreakers.
• Usethewireswhicharenotlighterthantheordinarypolychloroprene
sheathedexiblecord(codedesignation60245IEC57).
 
Main switch protection
Select the main switches in according to the next table:
Model Power supply
Max 
current (A)
CB  
(A)
ELB  
(nº poles/A/mA)
All Indoor 
Units  
(except 8, 
10, 16 and 
20HP)
1~ 230V 50Hz 
or 
1~ 220-240V 
50Hz (depending 
on the model)
5.0 6 
ELB: Earth leakage breaker; CB: Circuit breaker
Outdoor unit MC (A) CB (A)
ELB 
(nº poles/A/mA)
 22.5 25
 22.5 25
 22.5 25
 15.0 20
 15.0 20
 15.0 20
Electric wiring
PMML0545 rev.2 - 04/2021
16
EN