ENGLISH
Questions Description Default Value Range Steps Units Application
Notes
Controller Conguration S SC S80 M
Question 11
How many 
thermostats are 
installed?
0
0
1 - ○ ○ ○ ○
If question 3 has been 
answered with a different 
answer than “No”, 
Conguration Assistant task 
will have nished after this 
question, since the room 
thermostats have to be 
connected as “Wired” (Mixed 
conguration (Wireless + 
Wired) is not allowed).
The number of possible 
installed thermostats depends 
on the answers of question 3.
1
2
Question 12
How are they 
connected?
Wired
Wired
- - ○ ○ ○ ○
Only available when question 
11 has been answered with 
“1” or “2” and if one of the 
following conditions:
- question 1 answered as “Yes” 
and question 3 as “No”
- question 1 answered as “No” 
and question 3 as “No
Wireless
IMPORTANT:
•  Always start the conguration from the Master. In case of using “advanced conguration”, Room PC-ARFH should be congured 
before start the “check RT address” procedure.
•  After the question 3, information is send between the PC-ARFH, so for example:
 - If rst PC-ARFH has been congured as Master, the other PC-ARFH cannot be Master and it is blocked to answer only the 
Question 3.
•  After the question 4, information is send between the PC-ARFH, so for example:
 - If rst PC-ARFH has only 1 circuit, the other PC-ARFH cannot control zone 2.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
121