ENGLISH
 
Holiday Mode
REF Access Description
Default 
Value
Range Steps Units Application
Notes
Holiday Mode S SC S80 M
absentYear Year 2015 - - - ○ ○ ○ ○ -
absentMonth Month 1 1-12 1 Months ○ ○ ○ ○ -
absentDay Day 1 1-31 1 Days ○ ○ ○ ○ -
absentTime Returning time 0:00 0:00 ~23:50 00:10 Min. ○ ○ ○ ○ -
absentSetting Setting Temperature 21 5 - 35 1 ºC ○ ○ ○ ○ -
- Start holiday mode No No/Yes - - ○ ○ ○ ○ (*1)
- Stop holiday mode No No/Yes - - ○ ○ ○ ○ (*2)
? NOTE
•  (*1): If “Holiday mode” is not operating.
•  (*2): If “Holiday mode” is operating.
 
Air Eco Offset 
REF Access Description
Default 
Value
Range Steps Units Application
Notes
Air Eco Offset S SC S80 M
c1RTEcoOffset Circuit 1 3 1-10 1 - ○ ○ ○ ○ (*1)
C2RTEcoOffset
Circuit 2 3 1-10 1 - ○ ○ ○ ○ (*2)
? NOTE
•  (*1): If Controlled circuits (LCDL)= “C1” or “C1+C2”.
•  (*2): If Controlled circuits (LCDL)= “Room C2” or “C1+C2”.
 
Room Thermostats 
Available if Controller type (LCDM)= “Unit” or “Unit + Room” .
•  Thermostats Type   (*1)
•  Compensation Factors   (*2)
•  Room Temp Demand OFF   (*2)
•  Check RT Address   (*3)
•  Detected Circuits   (*3)
•  Thermostat 1   (*4)
•  Thermostat 2   (*4)
? NOTE
•  (*1):Visible only if Controller type (LCDM)= “Unit”. Wireless not available only if Controller type (LCDM)= “Unit”, If “Unit+Room” forced to wired.
•  (*2): If Water calculation modes (Water calculation mode for circuit 1 heating (C1WC)) or (Water calculation mode for circuit 1 cooling (CC1WC)) or 
(Water calculation mode for circuit 2 heating (C2WC)) or (Water calculation mode for circuit 2 cooling (CC2WC)) as not “Disabled” and (Thermostat 
type (RTType)= “Wireless” or “Wired” or Central mode (COT)= “Air” or  “Full”).
•  (*3): If Thermostat type (RTType)= “Wired” and Controller type (LCDM)= “Unit” or “Unit + Room”.
•  (*4): If Controller type (LCDM)= “Unit” and Thermostat type (RTType)= “Wireless”.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
137