ENGLISH
DSW1: Additional setting 0
Factory setting. No setting is required.
Factory setting
1~ 230V 50Hz 3N~ 400V 50Hz
DSW2: Unit capacity setting
No setting is required.
4.0 HP +3 6.0 HP
DSW3: Additional setting 1
Setting before shipment
1-step heater for 3-phase unit
DSW4: Additional setting 2
Setting before shipment
87
DHW defrost
87
Heater forced OFF
87
Unit and installation pipes antifreeze
protection
8
7
Standard / ECO water pump operation
8
7
Electric heater or boiler emergency mode
87
DHW tank’s heater operation
8
7
Open SV1/2 for vacuum and R-410A
refrigerant recovery function
87
Disabled R-134a compressor
87
C A U T I O N
Never turn all DSW4 dip switch pins ON. If this happens, the software
of the unit will be removed.
Never activate “Heater Forced OFF” and “Electric heater or boiler
emergency mode” at the same time.
DSW5: Additional setting 3
In the cases where the outdoor unit is installed into a location
where its own outdoor ambient temperature sensor can not
give a suitable temperature measurement to the system, it
is available the 2nd outdoor ambient temperature sensor as
accessory. By means of DSW1&2 setting, the preferable sensor
for each circuit can be selected.
Factory setting
Outdoor unit sensor for circuits 1 and 2.
Outdoor unit sensor for circuit 1; Auxiliary
sensor for circuit 2.
Auxiliary sensor for circuit 1; Outdoor unit
sensor for circuit 2.
Auxiliary sensor instead of outdoor unit
sensor for both circuits.
4-20 mA setting temperature
(Only manual operation)
Use the maximum temperature value
between Two3 (boiler / heater thermistor) and
Two (water outlet thermistor) for water control
DSW6: Not used
Factory setting
(Do not change)
DSW7: Additional setting 4
Factory setting (RWH-(V)NFE)
Factory setting (RWH-(V)NFWE)
Integrated DHW tank version
Defrost for the water electric heater