FireNETPlusWiringInstruction 5 V1.01
8. Ground Fault
A ground fault indication occurs when 30K Ohms or less is detected between earth
ground and the following field terminals of the FireNET Plus Panel:
24V OUT
AUX 24V
NAC1 and NAC 2
SLC1 and SLC2
NET IN and NET OUT
COMMS
9. Power Output Circuits
Special Application outputs are provided on the NAC1 and NAC2 terminals of the
FireNET Plus Panel.
10. Limited Energy Circuit
All circuits are power limited except for AC input/output and the battery.
11. Supervised Circuits
All circuits of the FireNET Plus Panel are supervised except relay terminals for the
TROUBLE, FIRE, SUPERVISORY and the TELCO.
12. SLC Circuits
SLC circuits of the FireNET Plus Panel operates with Hochiki’s DCP-Protocol.
Terminals
Description
SLC1 IN, SLC1 OUT
and SLC2 IN, SLC2 OUT
Signaling Line Circuits are Class A, Style 7, Class A, Style 6 or Class B,
Style 4.