FireNETPlusWiringInstruction 8 V1.01
15. Relay Circuits
The following is the specification for the FireNET Plus Panel Relays:
Parameter
Description
Operation
Common: Operates for all of the signals relative to its type (such as alarm, trouble, supervisory).
Current
1A maximum, volt free change over contact
Voltage
30 VDC max
Power Factor
1.0 PF
16. Auxiliary Voltage Circuits
The following is the specification for the FireNET Plus Panel Auxiliary Voltage Circuits:
Terminal
Description
24V OUT
Regulated 24 VDC @ 360 mA max
AUX 24V
Regulated 24 VDC @ 360 mA max