Sequence of Operation Con't
buttons to select a trip current appropriate for
the application. Range is
The current trip value is determined by selecting the
allowed overcurrent percentage and using the following formulas:
the trip value for an 8% over current, to protect a
motor with an FLA of 6.5 amps:
= (8% + 100%) / 100 = 1.08
= 1.08 times 6.5 amps = 7.02 amps.
Use a trip value of 7.0 amps.
button after selecting the
ENTER button after selecting the ENTER
option, in step 4 above, the next
buttons to choose a percent phase imbalance ranging
from 2% to 100%. Press the
ENTER button when correct. The ENTER
The next display will be "
Phase Imbalance Delay provides an operator selectable time delay
cially useful during part (split) winding motor startup. The time
can be varied from 2.0 to 30.0 seconds in 0.5 second
buttons to choose a phase imbalance
ENTER button when correct. ENTER
option in step 4 above, the next
is verified each time line voltage is applied to the load. The time
Phase Imbalance Delay menu above, is used Phase Imbalance Delay
as the delay time employed before phase order is checked. Use the
ENTER button. The default is "ENTER
The menu should have returned to the Home Screen. Now
button three times. The display should indicate
MODE button three times. The display should indicate MODE
Temperature Trip Settings
button. The display should indicate “
ENTER button. The display should indicate “ENTER
ENTER button. The default is ENTER
” in the previous step, the next display
choose the type of sensor
ENTER button. The default is ENTER
buttons to select the desired high temperature exhaust trip value
ENTER button to save ENTER
the value. The default is "
buttons to select the desired high temperature exhaust trip resis-
button to save the value. The default is "
ENTER button to save the value. The default is "ENTER
buttons to select the desired high temperature exhaust trip resis-
button to save the value. The default is "
ENTER button to save the value. The default is "ENTER
ENTER button. The default ENTER
" in the previous step, the menu should
have returned to the Home Screen. Now press the "
button four (4) times. The display should indicate "
" in step 15 above, the next display will
ENTER button. The default is ENTER
high and low temperature trip high and low
button to continue. The default is
ENTER button to continue. The default is ENTER
" temperature in the previous screen,
the next display will be "
buttons to select the desired high oil trip temperature
buttons to select the desired low oil trip temperature value in
ENTER button to save the ENTER
" high and low temperature trip points
the next display will be "
buttons to select the desired
The next display should be "
buttons to select the desired low oil trip
button to save the value.
ENTER button to save the value. ENTER
" high and low temperature trip values
ENTER button to continue. ENTER
in the previous test step,
overcurrent percentage + 100%