(page 13) to connect the exhaust sensor's wires to the
terminals on the Model 610. Either exhaust sensor wire
an be connected to either of the EXHS+ or
When using two (2) Model 610 Digital Current Monitors
for the Dual Model 610 Part (Split) Winding Motor installation,
the exhaust sensor wires to
addresses will be different. Therefore,
610's register data, excluding the Modbus addresses,
(page 17) for selecting the exhaust sensor's
Model 610's exhaust sensor hardware
Select a mounting configuration that provides a safe and
reliable temperature signal for the application. Always select a
temperature sensor that exceeds the highest and lowest expected
oil temperature(s). When available, select a wire length longer than
required for the application.
If additional wire is needed, use 22AWG (minimum) shielded
stranded, twisted pair cable properly insulated for the application.
The maximum length of additional
longer distances, consult factory.
Follow the oil temperature sensor manufacturer's instructions
and recommendations when installing the oil sensor on / in the
After mounting the sensor, refer to
Exhaust Sensor, Oil Sensor and Modbus Wiring Diagram
to connect the oil sensor's wires to the
nals on the Model 610. Either sensor wire can be connected to
either of the OIL+ or OIL- terminals.
When using two (2) Model 610 Digital Current Monitors for
the Dual Model 610 Part (Split) Winding Motor installation,
addresses will be different. Therefore,
610's register data, excluding the Modbus addresses,
steps 14 thru 31 for selecting the oil sensor's
Model 610's oil sensor hardware installa-
Modbus RTU Installation
Model 610 Exhaust Sensor, Oil
Sensor and Modbus Wiring Diagram,
The Model 610's Modbus terminals are defined as:
When using two (2) Model 610 Digital Current Monitors for
the Dual Model 610 Part (Split) Winding Motor installation,
the Modbus RTU connection to
addresses will be different. Therefore,
610's register data, excluding the Modbus addresses,
Model 610's Modbus hardware installa-
Verify (double check) all Model 610 controller(s) and motor
contactor(s) motor (load) wiring.
Disable the motor contactor's ability to activate, by
removing and protecting the
rarily removing and protecting the rarily
24 VAC motor contactor's coil
terminal on the Model 610's
relay if using two (2) Model 610s
Apply 24 VAC power to the controller(s) and line power to
the motor contactor(s). Verify the motor contactor(s) do not ener-
gize the motor. Also verify the LCD screen shows 0.0 amps.
Turn off both the controller's 24 VAC power
to the motor contactor(s).
(removed in step 2 above)
Apply 24 VAC power to the single Model 610 controller or,
Apply line power to the motor contactor(s).
If the motor being protected has an FLA greater than 10
LED comes on, within the number of
14), and that the motor contactor(s) has / have disconnected line
If the motor's FLA is greater than 10 amps a
disconnect line voltage to the motor
disconnect line voltage to the motor, disconnect line voltage to the motor
the line voltage going to the motor contactor(s) and verify the
motor turns off. Then go to step 13 on page 16.
The 610's LCD display should indicate
that occurred. If the trip was due to over current, then the Model
610 Control(s) and motor contactor(s) wiring has been installed
correctly and both devices are working properly.
If the controller tripped due to any other reason, such
Exhaust Temperature Sensor
Installation Con't
Initial Checkout Procedure
Oil Temperature Sensor
Installation