20K Ohms Depending on Sensor Type; 0 is Used When Low
Max Number Of Auto Resettable Trips
Allowed Before a Lockout Occurs
Read & Write; Baud Rate Codes: 0 = 1200; 1 = 2400; 2 = 4800,
3 = 9600; 4 = 19,200; 5 = 38,400; 6 = 57,600; 7 = 115,200
Read & Write; Parity Codes are:
38 = Even Parity, With 1 Stop Bit.
54 = Odd Parity, With 1 Stop Bit.
14 = No Parity With 2 Stop Bits.
Read & Write; Codes: 0 = Alarm on Every Trip; 1 = Alarm When
Lockout Occurs; 2 = Alarm When a Trip Occurs After the Previ-
ous Lockout Has Been Reset.
of Trips Since Last Manual
Read Only; Range = 0 to Maximum Selected Number Of Auto-
0 to 440 Amps (All values times 10)
0 to 440 Amps (All values times 10)
0 to 440 Amps (All values times 10)
Read Only; Codes: 0 = None; 1 = Current; 2 = Phase Imbalance;
3 = Exhaust Temp High; 4 = Oil Temp High; 5 = Modbus Initi-
ated Trip; 6 = Phase Order Incorrect; 7 = Oil Temp Low;
8 = Exhaust Sensor Bad; 9 = Oil Sensor Bad.
Read Only; Units in Amps, or % Phase Imbalance, or
Read Only; Range = 0 to 32,000 Hours.
Time Until Trip Will Auto Reset
Read Only; Range = 0 to 255 Minutes
Initiate Restore to Factory Settings
Write Only; 1 = Yes or 0 = No
Read & Write; Range 4 to 60 (in 1/2 sec units, 2 - 30 seconds)