as phase imbalance, phase order, or temperature out of range,
correct the problem(s) before re-applying line voltage to the motor
section (on pages 3 thru 9
the appropriate wiring diagram(s)
shoot and correct the problem(s) that allowed the motor to keep
occurred. After each repair, the installer
Initial Checkout Procedure
16 - 19) to ensure the repair fixed the problem(s).
Once the Model 610 Digital Current Monitor(s) and motor
contactor(s) is /are working correctly, the installer can
current trip level to the desired value for the application, (typi-
). See steps 1 thru 5 in the
” section (pgs 16 & 17) for the procedure.
You may now manually reset the Over Current Trip by pressing
MODE button once and then the MODE
If a three (3) phase motor runs backwards, the installer must
turn off line power to the motor and 24 VAC to the Model 610,
wires going to the motor and also swap
wires at the Model 610’s terminal block.
Phase order verification can be turned off, using the
menu system. Refer to the
Model 610 Digital Current Monitors, P/N Model
610-1PH(MOD) & P/N Model 610-3PH(MOD)
Modbus Slave that responds to a Modbus Master, which can send
requests to read the Model 610's internal register data or write
new data into the 610's internal registers. The Modbus connection
to the controller is an industry-standard three wire Modbus RTU
(Remote Terminal Unit) RS-485 serial data link that can be shared
with other modbus capable controllers and sensors.
here are 32 Modbus internal data registers (numbered 0 - 31)
available in this controller, as listed in
610 Modbus Register Data Information,
Modbus register contains 16 data bits which can be updated using:
Modbus command 03, to read the data from one or more,
of the 610's internal data registers at a time.
Modbus command 16 (hexadecimal 10), to write data to
internal data registers at a time.
Modbus command 06, to write data to a single internal
ll of the Model 610 Digital Current Mon-
itor's mode, menu and submenu parameters and numerical
remotely, proceed with the following steps
address, baud rate and parity for
Write to each slave using the
register numbers and associated data, as required, to set up
's operating parameters and numer
for a brief period of time
before reviewing all the data contained in the 32 internal
, to ensure correct operation.
The default Modbus settings, stored within the controller, are:
• Modbus slave address = 1.
, or follow the steps below to review or update
any or all the parameters and numerical values used by the Model
610. All settings and values are stored and saved within the control-
With line power, to the motor contactor, turned off and with
24VAC power applied to the Model 610
• Verify no error messages are displayed on the LCD.
button twice. The display should indicate
MODE button twice. The display should indicate MODE
button. The display should indicate
ENTER button. The display should indicate ENTER
buttons to select the number of
current transformer phases that are connected to the controller.
temperature sensing is desired.
ENTER button. The default is ENTER
The display should read: “
Sequence of Operation
Initial Checkout Con't
If any of the down loaded Modbus data is incorrect, the
Model 610 Digital Current Monitor's microcontroller
will change the incorrect data into software selected
default values during the Model 610's next operating
cycle. Therefore, after updating any data remotel
cycle. Therefore, after updating any data remotely,cycle. Therefore, after updating any data remotel
allow the Model 610 to operate
before reviewing ALL of the data con-
brief time period before reviewing ALL of the data con-brief time period
to 1) ensure that all of the operating parameters and
numerical values, needed for the application, have been
correctly selected and 2) also ensure that any unneeded
or undesired options or numerical values have not
inadvertently been left selected.
Phase imbalance can be caused when single phase
loads are not distributed evenly throughout a 3
Modbus RTU Operation