13
MODBUS RTU
ADDRESS
DATA CONTENTS
DATA TYPE and RANGE
0
Trip Amps Times 10
Read & Write; Range = 5 to 200 Amps (All values times 10)
1
Number
Of Current Transformers Used
Read & Write; Codes: 1 = Single Phase; 3 =  ree Phase;
0 =
Temperature Only,
No Current Transformers Used.
2
Phase Imbalance Trip % (3 Phase Only)
Read & Write; Range =1% to 100%
3
Check Phase Order (3 Phase Only)
Read & Write; 1 = Yes
o
r
0= No
4
Auto Reset Delay Time
Read & Write; Range = 0 to 255 Minutes.
5
Use Exhaust Temperature Sensor
Read & Write; 1 = Yes
o
r
0= No
6
Exhaust Sensor Type
Read & Write; Codes: 0 = Omega 10K; 1 = PTC Resistance;
2 =
NTC Resistance.
7
Exhaust
Trip Temp Value
Read & Write;
Range =
8
0
°
F
to
300
°
F
or 100 Ohms to
20K Ohms Depending on Sensor Type (All values times 10)
.
8
Use Oil Temp
Read & Write; 1 = Yes
o
r
0 = No
9
Oil Sensor Type
Read & Write; Codes: 0 = Omega 10K; 1 = PTC Resistance;
2 =
NTC Resistance
.
10
Oil High Temp
Trip
Value
Read & Write;
Range = 0 or
2
0
°
F
to
200
°
F
or 200 Ohms to
20K Ohms Depending on Sensor Type; 0 is Used
W
hen
When W
High Temp Not Selected
.
Model
610 Modbus
Register
Data Information
TABLE
6A









































