Honeywell Home DR90A3000 - Wiring Diagram for DG115 IAQ Control

Honeywell Home DR90A3000
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Terminal Description
NOTE: The outer screws on the terminal block
secure the block to the chassis. They are not used
for wiring.
A wiring terminal block is located on the side panel
of the dehumidifier unit.
The six terminals for the terminal block (reading
from left to right in the photo) are:
FL
OAT:
External low voltage float switch or
w
ater sensor (two terminals). Use
normally closed switch.
DHUM:
Compres
sor and fan operation for
dehumidification
R:
DR90/DR120 24V output
F
AN:
F
an activation only for ventilation
C:
DR90/DR120 24V output
External 24V devices can be powered from R and C
terminals (20V
A max.).
Wiring
Wire the DR90A3000/DR120A3000 according to the diagram that applies to your
desired operation.
DR90A3000/DR120A3000 Dehumidification System 33-00298EFS—09
8
Follow this diagram if using
the Prestige thermostat.
DEHUMIDIFIER
DHUM
+
+
R
FAN
C
FLOAT
IN THIS DIAGRAM, U1 CONTROLS THE DR90/DR120 FOR DEHUM AND
U2 CONTROLS THE DR90/DR120 FOR VENTILATION.
INSTALL A JUMPER ON EIM AS SHOWN ONLY WHEN USING THE
DR90/DR120 FOR VENTILATION IN ADDITION TO DEHUMIDIFICATION.
IF A FLOAT SWITCH IS NOT USED, THEN JUMPER THE FLOAT TERMINALS
.
1
2
1
2
3
3
EIM
U3
U3
U2
U2
U1
U1
M38418A
CAUTION: Low voltage hazard.
Can cause equipment damage.
Disconnect HVAC equipment before beginning installation.