EasyManuals Logo

Honeywell ComfortPoint Open CPO-VAV2A User Manual

Honeywell ComfortPoint Open CPO-VAV2A
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
TERMINAL SETTINGS
9 EN1B-0022 IE10 R0717
CP-US-WM-VAV
CP-WM-VAV
The connection between CPO-VAV2A and wall modules are
illustrated in Figure 15 through Figure 21.
Figure 15 Connection of T7460 with the CPO-VAV2A
Figure 16 Connection of T7560 with CPO-VAV2A
Figure 17 Connection of C7710D with CPO-VAV2A
Figure 18 Connection of C7262A with CPO-VAV2A
Figure 19 Connection of CP-CM with CPO-VAV2A
Figure 20 Connection of CP-WM-VAV with CPO-VAV2A
Figure 21 Connection of TR40 and TR42 with CPO-VAV2A
Attention
Resolution of the PT1000 sensor: 1 Fahrenheit or
0.6 Centigrade.
Do not use the datapoint associated to PT1000 in
control logic which requires a resolution less than
1 Fahrenheit.
The analog input with PT1000 can be used in
control loops only when connected to
CPO-VAV2A via a transducer with 0-10V rating.
Additionally, you must use the ComfortPoint Open
Studio tool to define custom characteristics which
matches the selected transducer.
The PT1000 sensors connected directly with
CPO-VAV2A can be used only for monitoring and
reporting purposes.
Attention
The CPO-VAV2A controller does not control the
LCD display of the T7560 Wall module. It handles
the temperature sensor input, Bypass/Fan, or Fan
Control Input. The LCD Display must not be used
to get the Effective Occupancy state of the
controller.
COM
SENSOR
SETPOINT
BYP/FAN
LED
BYP/RTN
LED/RTN
T7460
Terminals
AGND
Temp
Set Point
ByPass/Fan
LED
VAV
Terminals
1
2
3
4
5
6
7
1
2
3
4
5
COM
SENSOR
SETPOINT
BYP/FAN
LED
Bypass**
Humidity
T7560
Terminals
AGND
Temp
Set Point
ByPass/Fan
LED
VAV
Terminals
1
2
3
4
5
6
7
1
2
3
4
5
24 Vac
8
COM
CO2 Output 0...10V
24 VAC/DC
NTC 20kOhm
SETPT. 1...10kOhm
LED INPUT
OCCUPANCY
C7110D
Terminals
AGND
Temp
Set Point
ByPass/Fan
LED
VAV
Terminals
1
2
3
4
5
6
7
1
2
5
6
AGND
A1
3
4
V+
Com AC/DC
TEMP
TEMP
OUT1: CO2
OUT2: CO2
RELAY NO
C7262A
Terminals
AGND
Temp
Set Point
ByPass/Fan
LED
VAV
Terminals
1
2
3
4
5
6
7
1
2
AGND
A1
4
RELAY NO
3
Common
Setpoint
MSTP+
Temperature Sensor
MSTP-
24 Vac/dc input
CP-CM
Terminals
AGND
Temp
Set Point
ByPass/Fan
LED
VAV
Terminals
1
2
3
4
5
6
1
2
3
24 Vac/dc input
Occupancy
(24Vac input contact)
Temperature Sensor
Setpoint
FAN/Bypass
Common
CP-WM
Terminals
AGND
Temp
Set Point
ByPass/Fan
LED
VAV
Terminals
1
2
3
4
5
6
1
2
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ComfortPoint Open CPO-VAV2A and is the answer not in the manual?

Honeywell ComfortPoint Open CPO-VAV2A Specifications

General IconGeneral
BrandHoneywell
ModelComfortPoint Open CPO-VAV2A
CategoryController
LanguageEnglish

Related product manuals