2.2.2 General Power Supply Notes:
Supply power is measured on a 10-minute interval (battery / external supply voltages)
An Item is not used to choose between externally supply and battery powered
For Alarm triggering three (3) consecutively low readings are required to the trip the associate
Alarm. This is done to help guard against falsely setting alarm due to a supply glitch
The Low Battery Voltage Alarm (Item 99) will not set if there is an External Supply voltage at
TB1 greater than the Battery voltage by over 1.0 volt
2 Powering the ERX 350
Honeywell | 4